Article 625.43 EVSE Disconnecting Means

Published on 19 September 2024 at 09:46

625.43 Disconnecting Means

Level 1 EVSE chargers less than 150 volts to ground require a readily available disconnecting means?

A)True

B)False

 

Answer is B)False

625.43 Disconnecting Means

For EVSE and WPTE rated more than 60 amperes or more than 150 volts to ground, the disconnecting means shall be provided and installed in a readily accessible location. If the disconnecting means is installed remote from the equipment, a plaque shall be installed on the equipment denoting the location of the disconnecting means. The disconnecting means shall be lockable open in accordance with 110.25