625.43 Disconnecting Means
Level 1 EVSE chargers less than 150 volts to ground require a readily available disconnecting means?
A)True
B)False
Answer is B)False
625.43 Disconnecting Means
For EVSE and WPTE rated more than 60 amperes or more than 150 volts to ground, the disconnecting means shall be provided and installed in a readily accessible location. If the disconnecting means is installed remote from the equipment, a plaque shall be installed on the equipment denoting the location of the disconnecting means. The disconnecting means shall be lockable open in accordance with 110.25
Add comment
Comments