230.24(B) Services

Published on 24 September 2024 at 20:23

Overhead service conductors, where not in excess of 1000 volts, nominal, shall have the following minimum clearance from final grade:

  1. 3.0 m (10 ft) - at the electrical service entrance to buildings, also at the lowest point of the drip loop of the building electrical entrance, and above areas or sidewalks accessible only to pedestrians, measured from final grade or other accessible surface only for overhead service conductors supported on and cabled together with a grounded bare messenger where the voltage does not exceed 150 volts to ground
  2. 3.7 m (12 ft) - over residential property and driveways, and those commercial areas not subject to truck traffic where the voltage does not exceed 300 volts to ground
  3. 4.5 m (15 ft) - for those areas listed in the 3.7 m (12 ft) classification where the voltage exceeds 300 volts to ground
  4. 5.5 m (18 ft) - over public streets, alleys, roads, parking areas subject to truck traffic, driveways on other than residential property, and other land such as cultivated, grazing, forest, and orchard
  5. 7.5 m (241/2 ft) over tracks of railroads