440.12(C) Small Motor-Compressors
For small motor compressors not having the locked rotor current marked on the nameplate, or for small motors not covered by table 430.247, table 430.248, table 430.249, or table 430.250 the locked rotor current shall be assumed to be six times the the rated load current.